A food factory or cold store becomes a major hazard installation when the anhydrous ammonia on site reaches 15 tonnes. Under Annexure A of the Major Hazard Installation Regulations, 2022, 15 tonnes makes it a low hazard establishment, 50 tonnes a medium hazard establishment and 200 tonnes a high hazard establishment. Each step up adds duties, from registration and an approved inspection authority risk assessment at the bottom to a safety report and a licence to operate at the top.
Ammonia is still the refrigerant of choice in large South African cold stores and abattoirs, and in many dairies and packhouses. Many sites have never added up how much they hold, and the figure is often larger than the engineering manager expects once every system and the cylinders in store are counted.
If the person who answers to the inspector has never been trained on the regulations, our South African Occupational Health and Safety Law course covers them, with a lesson on when the MHI Regulations reach a food site and another on the ammonia plant itself.
In short
- The thresholds for anhydrous ammonia (UN 1005) are 15 tonnes (low hazard), 50 tonnes (medium) and 200 tonnes (high), counted per establishment.
- Count the maximum quantity that may be present at any one time: the full charge of every system, wherever it sits, plus spare stock and cylinders.
- Every class needs a designated responsible person, registration, a risk assessment by an approved inspection authority to SANS 1461 at least every five years, and an on-site emergency plan to SANS 1514 tested at least once a year.
- Medium hazard sites add a major incident prevention policy. High hazard sites add a safety report and a licence to operate.
- Below 15 tonnes the Act can still treat a plant as a major hazard installation, and other toxic substances on site are added to the ammonia.
When ammonia refrigeration makes a site a major hazard installation
The Major Hazard Installation Regulations, 2022 were published as Government Notice R.2989 in Government Gazette 47970 on 31 January 2023. They repealed the 2001 regulations. Regulation 26 leaves commencement to a date set by the Minister, but the Department of Employment and Labour announced their application on 17 May 2023 and gave existing installations a transition period from 1 February 2023 to 1 January 2025.
Chapter 1 of Annexure A names ammonia anhydrous, UN number 1005, with qualifying quantities in tonnes. The definitions turn those quantities into three classes.
| Ammonia on site | Class | What changes |
|---|---|---|
| Less than 15 tonnes | Not classified | The OHS Act and its other regulations still apply |
| 15 tonnes to less than 50 tonnes | Low hazard | All except regulations 11 (prevention policy), 12 (safety report) and 13 (licence) |
| 50 tonnes to less than 200 tonnes | Medium hazard | All except regulations 12 and 13 |
| 200 tonnes or more | High hazard | All, including the safety report and licence to operate |
The quantity below 15 tonnes is not a safe harbour.
Section 1 of the Occupational Health and Safety Act defines a major hazard installation as one where more than the prescribed quantity is or may be kept, or where a substance is produced, processed, used, handled or stored in a form and quantity that has the potential to cause a major incident. The fee schedule in Annexure B has a separate line for a site “considered an MHI”, which appears to cover sites in that position.
How to count the ammonia on your site
Regulation 4 asks for a statement of the envisaged maximum quantity of all dangerous substances that may be present at the establishment at any one time. For an ammonia plant that means the total inventory of every system on the site, wherever it sits, plus any spare stock in separate vessels and any cylinders kept for top ups. Pumping a system down moves its charge into the receiver without adding to it, so count it once.
Your refrigeration contractor’s design data and charge records are the place to start. Purchase records over the past few years are a useful check.
Note 16 of Annexure A says a quantity of 2% or less of the qualifying quantity must be ignored when totalling, but only if its location means it cannot start a major incident elsewhere on the site. Borderline cases should be discussed with the approved inspection authority.
The Annexure also adds substances together. The rule is applied separately for toxicity, flammability and eco-toxicity, so ammonia counts with other toxic substances such as chlorine, which qualifies at 5 tonnes for low hazard. A site with 12 tonnes of ammonia and 1 tonne of chlorine scores 12/15 plus 1/5, which is 0.8 plus 0.2, or 1.0, and is a low hazard establishment even though neither substance reaches its own threshold.
A worked example: a cold store at 16 tonnes
Take a frozen food distributor in Ekurhuleni with two engine rooms. The design data shows a total charge of 10.6 tonnes in the main plant, receiver included, and 4.8 tonnes in the blast freezer plant. The store also keeps four cylinders of 68 kg each for top ups, which is 0.27 tonnes.
The maximum that may be present at one time is 10.6 plus 4.8 plus 0.27, or 15.67 tonnes. The cylinders are below 2% of 15 tonnes (0.3 tonnes), but they are stored in the engine room next to the main plant, where a fire could involve both, so the 2% rule does not let them go. Even without the cylinders the site holds 15.4 tonnes. It is a low hazard establishment.
In practice that site now needs a designated responsible person, registration with the chief inspector and an approved inspection authority risk assessment. It also needs a newspaper advertisement with community notices, and an on-site emergency plan approved by the municipality.
If the planned extension adds another freezer plant with 6 tonnes, the total passes 21 tonnes, which is still low hazard, and the Form A notification goes in 90 days ahead with proof of land use approval. Reaching 50 tonnes would make it a medium hazard establishment and bring in the prevention policy. A move to a low charge packaged plant or a secondary refrigerant could take the site back below 15 tonnes, which is a decision worth costing before the next expansion.
What every registered ammonia site must have
Whatever the class, these are the documents and arrangements an inspector or the municipality can ask to see.
| Duty (regulation) | What it means on site |
|---|---|
| Responsible person (3) | Designated in writing, full time, for every premises. Deputies may be appointed |
| Notification on Form A (4) | 90 days before erecting an establishment or making a change, to the chief inspector, the provincial office and the municipality |
| Public notice (4(4) and 4(5)) | Newspaper advertisement in English and the predominant local language, plus notices in the community. The public has 60 days to make representations |
| Registration certificate (5 and 6) | Valid five years, displayed conspicuously. R350 for a low, R400 for a medium and R450 for a high hazard site (Annexure B) |
| Risk assessment (10) | Done by an approved inspection authority to SANS 1461, at intervals not exceeding five years or on change. A copy is kept on site |
| On-site emergency plan (15) | To SANS 1514, approved by the municipality, tested at least once a year and reviewed at least every three years |
| Incident reporting (16) | A major incident, or any incident that activated the emergency plan, reported to the chief inspector within 48 hours. Preliminary report within seven days, final report within six months. All near misses investigated and recorded in a register |
| Training and induction (17) | All employees trained, refreshed after a change. Contractor and visitor induction valid for no more than 12 months |
Whoever holds this file should know the Act behind it. Our South African Occupational Health and Safety Law course takes about 7 hours online and covers the MHI Regulations, the Pressure Equipment Regulations and the ammonia plant.
Medium hazard sites must also keep a written major incident prevention policy, reviewed every five years or on change, with a process safety management system behind it. High hazard sites need a safety report kept for the life of the establishment and a licence to operate. Regulations 11(2), 12(5) and 13(2) gave existing sites 36 months from entry into force for these. Whether counted from publication or from the Department’s May 2023 announcement, those periods have now run out, so if they are not done, speak to your provincial office.
Two other sets of rules sit beside the MHI Regulations on every ammonia site, whatever the quantity: the Pressure Equipment Regulations for the plant and the Regulations for Hazardous Chemical Agents, 2021 for exposure. Our post on hazard identification and risk assessment in a food factory shows how they fit into one HIRA.
The food safety side of an ammonia leak
An ammonia release is a health and safety emergency first, but it is also a food safety event. Ammonia dissolves readily in water and raises the pH of moist surfaces, so unwrapped and high moisture product near a leak can pick up off odours and discolour. Packaging decides most outcomes. Sealed glass and cans, or intact film, usually protect the product. Cartons and open product do not. Your FSSC 22000 or BRCGS emergency procedure should say who decides what happens to exposed stock, how it is held and assessed, and what records are kept before anything is released.
Our Emergency Preparedness and Response Risk Assessment Template (RA21) gives you a structure to complete for your site, covering contamination and utility loss events. Add the ammonia release scenario. It sits beside your SANS 1514 on-site plan and does not replace it. If the plant is coming back from a shutdown, our guide to restarting a food factory after the December shutdown covers the food safety checks. For the people side, our Hazard Identification, Risk Assessment and Incident Investigation course trains supervisors and SHEQ officers to investigate a near miss properly, which regulation 16 requires on a registered site and clause 10.2 of ISO 45001:2018 already expects of a certified one.
Why food businesses choose ASC
Rated 4.9 out of 5 from more than 400 Google reviews across our three offices.
Gqeberha Google reviews Johannesburg Google reviews Cape Town Google reviews
Our online courses hold a 4.9 average from 2,659 course reviews and more than 7,200 course enrolments.
ASC is ISO 9001 certified, a SAATCA registered online training course provider (TC 065), FoodBev SETA Accredited Provider No. 587/00337/1900 and an Exemplar Global Recognised Training Provider.
Know what the inspector will ask
South African Occupational Health and Safety Law
Built for the people who answer to the inspector. The course works through the OHS Act and its regulations as they apply on a food site, including lessons on the Pressure Equipment Regulations and the ammonia plant, the Regulations for Hazardous Chemical Agents, and when the Major Hazard Installation Regulations reach a food site. About 7 hours online, self paced. R1,495, no VAT added. Less than one day of a stopped engine room.
Enrol in the course WhatsApp us about team seats
Writing the food safety side of your emergency plan? Emergency Preparedness and Response Risk Assessment Template (RA21) (R690, instant download).
Questions we are often asked
How much ammonia makes a site a major hazard installation in South Africa?
Under Annexure A of the Major Hazard Installation Regulations, 2022, 15 tonnes of anhydrous ammonia makes a site a low hazard establishment, 50 tonnes a medium hazard establishment and 200 tonnes a high hazard establishment. A smaller plant can still be a major hazard installation under the OHS Act if it has the potential to cause a major incident.
Who carries out the MHI risk assessment?
Regulation 10 requires the risk assessment to be carried out by an approved inspection authority in accordance with SANS 1461, after consulting the health and safety representatives or committee, at intervals not exceeding five years or when the establishment changes.
How often must an ammonia site test its emergency plan?
Regulation 15 requires the on-site emergency plan to be tested or exercised at least once a year, with the municipality invited to take part, and reviewed at least every three years.
Does the MHI registration replace other OHS duties?
No. The Pressure Equipment Regulations, the Regulations for Hazardous Chemical Agents and the rest of the OHS Act still apply to the plant and the people who work near it.
Sources
- Department of Employment and Labour, GN R.2989, Major Hazard Installation Regulations, 2022, Government Gazette 47970, 31 January 2023
- Department of Employment and Labour, Major Hazard Installers now have ninety days to notify authorities, media statement, 31 October 2023
- Occupational Health and Safety Act 85 of 1993, section 1, definitions of major hazard installation and major incident